HTP, Ex e Polyamide cable glands

The HTP polyamide cable glands for non-armoured cables have an impact resistance of 7 joules and are characterised by easy assembly. The cable glands can be used in both gas and dust atmospheres.

Included in delivery

including silicone flat washer and dust cap

Technical Data

Atmosphere

G/D

Zone

1

2

21

22

Type of ignition protection

Ex eb

Ex tb

Equipment group

II

Category

2/3

Material

Polyamide 6

Certificates

IMQ 18 ATEX 025 X

IECEx IMQ 18.0006X

Ingress protection

IP 66

IP 68 to EN 60529

Impact resistance

7 Joule to EN 60079-0

Cable types

non-armoured cables

Temperature range

-60°C to +70°C

Product Range
Order-No.TypeCable ØWrench SizeThread LengthDatasheetInquiry
08.21 11 12 M 12 x 1.5 4 - 6,5 15 mm 15 mm 15 mm, 15 mm, 15 mm

08.21 11 13 M 12 x 1.5 4 - 6,5 10 mm 15 mm 15 mm, 15 mm, 15 mm

08.21 11 16 M 16 x 1.5 5 - 8 10 mm 19 mm 19 mm, 19 mm, 19 mm

08.21 11 17 M 16 x 1.5 6 - 10 15 mm 22 mm 22 mm, 22 mm, 22 mm

08.21 11 20 M 20 x 1.5 7 - 12 10 mm 24 mm 24 mm, 24 mm, 24 mm

08.21 11 21 M 20 x 1.5 7 - 12 15 mm 24 mm 24 mm, 24 mm, 24 mm

08.21 11 22 M 20 x 1.5 11 - 14 15 mm 27 mm 27 mm, 27 mm, 27 mm

08.21 11 24 M 25 x 1.5 14 - 18 15 mm 33 mm 33 mm, 33 mm, 33 mm

08.21 11 25 M 25 x 1.5 12 - 17 15 mm 29 mm 29 mm, 29 mm, 29 mm

08.21 11 32 M 32 x 1.5 16 - 21 10 mm 36 mm 36 mm, 36 mm, 36 mm

08.21 11 33 M 32 x 1.5 19 - 25 15 mm 42 mm 42 mm, 42 mm, 42 mm

08.21 11 40 M 40 x 1.5 23 - 32 18 mm 53 mm 53 mm, 53 mm, 53 mm

08.21 11 50 M 50 x 1.5 31 - 38 18 mm 60 mm 60 mm, 60 mm, 60 mm

08.21 11 63 M 63 x 1.5 35 - 44 18 mm 65 mm 65 mm, 65 mm, 65 mm